Intermediate Class Medium Voltage
Ultra-Fast Surge Arrester

Description

Screenshot 2025-01-17 at 08.20.23.png

The UFSA is designed not to require maintenance. All UFSA units have been tested to 10 or more EMP pulses at the manufacturing facility.

 

While testing and maintenance are not required, if every other year you want to check the UFSAs, wait
until your system is down for lightning surge arrester maintenance, you can do a quick check to see if any
changes to the UFSA readings have changed more than 3 standard deviations from the data in Table 1
above.

 

The tests must be done with the UFSA disconnected from your system and the equipment to do the tests
is listed below.

​

  • Megger – Model 1625 or equivalent

  • Frequency response analyzer (BODE plot from 500 kHz to 5 MHz)

  • Standard 1:1 scope probe

  • Current probe – Keysight DXO1204 or equivalent

 

As an alternative to your testing, you may send the units to AFS, Doble Engineering or Omicron who offer
testing for Utility systems and equipment.


E1 verification requires the following equipment

 

  • Pulse generator (150 to 300 kV) capable of producing a Mil-125-188 Appendix B Pulse current

       (2.5 or 5 kA)

  • High voltage scope probes – Northstar PVM series

  • Current probes – Prodyn I-125-9A or equivalent

  • Oscilloscope – Keysight 6004A or equivalent

 

Another option to test for E1 is to purchase spares and return units to AFS for testing or arrange with
SARA, Oak Ridge National Labs, or Boeing Little Mountain test facilities for example.

Advanced Fusion System’s (AFS) Ultra-Fast Surge Arrester (UFSA) EMProve® is a grid protection device designed to shunt the induced current resulting from an E1 HEMP or IEMI event away from medium voltage equipment to ground.
During testing at a Nationally Recognized Test Lab (NRTL), the EMProve® shunted more than 97 % of the induced current surge to ground when tested under MIL-STD188-125.


Electrical connections are made to the UFSA by two sets of two NEMA compliant threaded holes.

​

Setup and Installation

 

  • The indoor EMProve® (model UFSAXXE1-A, see Fig. 1) is suitable for installation in equipment housings and inside buildings where pollution degree levels are very light to light. 

  • The outdoor EMProve® (model UFSAXXE1-B, see Fig. 2) is suitable for all installation locations exposed to the elements, where pollution degree medium to heavy.  

  • The EMProve® must not be used as a structural member for any other device or equipment.  

  • The EMProve® device is intended to be mounted to the phase conductors and neutral to a solid ground reference, ideally within 1 meter of the asset that is to be protected.

  • Due to the fast transient E1 pulse with high di/dt current flowing in the connecting leads, one must expect additional voltages to be developed in those connecting leads.  This will add to the E1 protect levels in Table 1 below, so it is important to have low inductance connecting cables.  A thin wide strap connections are preferred.

  • Example:  Assume the inductance of the connecting leads is 250 nH and the 2.5 kA/20 nS current is flowing in that lead, an additional 31 kV to the E1 protect level of the UFSA.

 

Environmental Specifications

​

 

  • Temperature range (storage/operating):  -40°F (-40 °C) to 150 °F (65 °C)   

  • Humidity: 5 % to 95 % (noncondensing) 

 

  • Electrical connections are made to the EMProve® by two NEMA compliant threaded holes on each connection flange. Various standard adapters are available at additional cost to facilitate electrical connections.  Custom adapters can be designed and fabricated.

  • It is suggested that the bottom conductor of the EMProve® (ground connection) be made with a rigid connection to support the device from below.  However, if impractical, a flexible wire or copper strap of suitable ampacity rating no longer than necessary may be used to make this connection.  

  • The top conductor of the EMProve®, phase connection may be made with either a low inductance flexible wire (or strap) of suitable ampacity rating no longer than necessary.

Part Number
Description
Rating
MCOV
8106.00001
UFSA06E1 INDOOR
6 kV
5.1 kV
8106.00002
UFSA06E1 OUTDOOR
6 kV
5.1 kV
8110.00002
UFSA10E1 OUTDOOR
10 kV
8.4 kV
8115.00002
UFSA15E1 OUTDOOR
15 kV
12.7 kV
8118.00002
UFSA18E1 OUTDOOR
18 kV
15.3 kV
8218.00002
UFSA18E1 OUTDOOR
18 kV
15.3 kV

*

**

81XX is an intermediate class arrester

82XX is a station class arrester

​

* Avail.  Q2 2025

**Avail. Q3 2025

​

For higher voltages, please contact us below.